The MultiPlus, as the name suggests, is a combined inverter and charger in one elegant package. Its many features include a true sine wave inverter, adaptive charging, hybrid PowerAssist technology, plus multiple system integration features.
Models:
800VA, 1200VA, 1600VA, 2000VA, 3000VA, 5000VA
VE Configure 3 basic | Victron Energy
- Unique PowerAssist feature
The MultiPlus will prevent overload of a limited AC source, such as a generator or shore power connection. First, battery charging will automatically be reduced when otherwise an overload would occur. The second level will boost the output of a generator or shore side supply with power taken from the battery.
- Uninterrupted AC power (UPS function)
In the event of a grid failure, or when shore or generator power is disconnected, the inverter within the Multi is automatically activated and takes over the supply to the connected loads. This happens so fast (less than 20 milliseconds) that computers and other electronic equipment will continue to operate without disruption.
- Virtually unlimited power thanks to parallel operation
Up to 6 Multis can operate in parallel to achieve higher power output. Three phase or split phase operation is also possible. Please check our datasheets to see which models have paralleling, three phase and split phase capabilities.
- Remote Monitoring and Control
When coupled with a GX device (e.g. Cerbo GX) you can monitor and control your Multi and system or systems' locally (LAN) or remotely via the internet from anywhere in the world, using the free VRM app and free VRM portal website. Access can be from a phone, tablet, laptop or PC for multiple operating systems. There is no end to the level of control, from adjusting your Multi to auto starting a backup generator and more...
MultiPlus 12 Volt 24 Volt
|
12/2000/80 24/2000/50
|
12/3000/120 24/3000/70
|
PowerControl
|
Yes
|
PowerAssist
|
Yes
|
Transfer switch (A)
|
50
|
Parallel and 3-phase operation
|
Yes
|
INVERTER
|
Input voltage range (V DC)
|
9,5 - 17 V 19 - 33 V
|
Output
|
Output voltage: 120 VAC ± 2% Frequency: 60 Hz ± 0,1% (1)
|
Cont. output power at 25°C / 77°F (VA) (3)
|
2000
|
3000
|
Cont. output power at 25°C / 77°F (W
|
1600
|
2400
|
Cont. output power at 40°C / 104°F (W)
|
1450
|
2200
|
Cont. output power at 65°C / 150°F (W)
|
1100
|
1700
|
Peak power (W)
|
4000
|
6000
|
Maximum efficiency (%)
|
92 / 94
|
93 / 94
|
Zero load power (W)
|
9 / 11
|
20 / 20
|
Zero load power in AES mode (W)
|
7 / 8
|
15 / 15
|
Zero load power in Search mode (W)
|
3 / 4
|
8 / 10
|
CHARGER
|
AC Input
|
Input voltage range: 95-140 VAC Input frequency: 45 - 65 Hz Power factor: 1
|
Charge voltage 'absorption' (V DC)
|
14,4 / 28,8
|
Charge voltage 'float' (V DC)
|
13,8 / 27,6
|
Storage mode (V DC)
|
13,2 / 26,4
|
Charge current house battery (A) (4)
|
80 / 50
|
120 / 70
|
Charge current starter battery (A)
|
4
|
Battery temperature sensor
|
yes
|
GENERAL
|
Auxiliary output (5)
|
n. a.
|
Yes (32A)
|
Programmable relay (6)
|
Yes (1x)
|
Yes (3x)
|
Protection (2)
|
a - g
|
VE.Bus communication port
|
For parallel and three phase operation, remote monitoring and system integration
|
General purpose com. port (7)
|
n. a.
|
Yes (2x)
|
Remote on-off
|
Yes
|
Common Characteristics
|
Operating temp. range: -40 - +65°C / -40 to 150°F (fan assisted cooling) Humidity (non-condensing): max 95%
|
ENCLOSURE
|
Common Characteristics
|
Material & Colour: aluminium (blue RAL 5012) Protection category: IP 21
|
Common Characteristics
|
M8 bolts
|
M8 bolts (2 plus and 2 minus connections)
|
Battery-connection
|
Screw-terminal 6 AWG (13 mm2)
|
M8 bolts (2 plus and 2 minus connections)
|
120 V AC-connection
|
Screw-terminal 6 AWG (13 mm2)
|
Screw-terminal 6 AWG (13mm2)
|
Weight
|
13 kg 25 lbs
|
19kg 40 lbs
|
Dimensions (hxwxd in mm and inches)
|
520x255x125 mm 20.5x10.0x5.0 inch
|
362x258x218 mm 14.3x10.2x8.6 inch
|
STANDARDS
|
Safety
|
UL 458, EN-IEC 60335-1, EN-IEC 60335-2-29
|
UL 1741, UL 458, EN-IEC 60335-1, EN-IEC 60335-2-29
|
Emission and Immunity
|
EN-IEC 61000-3-2/3-3/, EN-IEC 61000-6-1/6-2/6-3
|
EN-IEC 61000-3-2/3-3/, EN-IEC 61000-6-1/6-2/6-3
|
1) Can be adjusted to 50 HZ;
2) Protection key:
a) output short circuit
b) overload
c) battery voltage too high
d) battery voltage too low
e) temperature too high
f) 120 VAC on inverter output
g) input voltage ripple too high
3) Non-linear load, crest factor 3:1
4) At 75?F ambient
5) Switches off when no external AC source available
6) Programmable relay that can a.o. be set for general alarm, DC under voltage or genset start/stop function AC rating: 120 V/4 A DC rating: 4 A up to 35 VDC, 1 A up to 60 VDC
7) A.o. to communicate with a Lithium Ion battery BMS
|
MultiPlus
12 Volt
24 Volt
48 Volt
|
C 12/800/35
C 24/ 800/16
|
C 12/1200/50
C 24/1200/25
|
C 12/1600/70
C 24/1600/40
|
C 12/2000/80
C 24/2000/50
|
12/3000/120
24/3000/70
48/3000/35
|
24/5000/120 48/5000/70
|
PowerControl
|
Yes
|
Yes
|
Yes
|
Yes
|
Yes
|
Yes
|
PowerAssist
|
Yes
|
Yes
|
Yes
|
Yes
|
Yes
|
Yes
|
Transfer switch (A)
|
16
|
16
|
16
|
30
|
16 or 50
|
100
|
INVERTER
|
TER Input voltage range (V DC)
|
9,5 - 17 V 19 - 33 V 38 - 66 V
|
Output
|
Output voltage: 230 VAC ± 2% Frequency: 50 Hz ± 0,1% (1)
|
Cont. output power at 25°C (VA) (3)
|
800
|
1200
|
1600
|
2000
|
3000
|
5000
|
Cont. output power at 25°C (W)
|
700
|
1000
|
1300
|
1600
|
2400
|
4000
|
Cont. output power at 40°C (W)
|
650
|
900
|
1200
|
1400
|
2200
|
3700
|
Cont. output power at 65°C (W)
|
400
|
600
|
800
|
1000
|
1700
|
3000
|
Peak power (W)
|
1600
|
2400
|
3000
|
4000
|
6000
|
10.000
|
Maximum efficiency (%)
|
92 / 94
|
93 / 94
|
93 / 94
|
93 / 94
|
93 / 94 / 95
|
94 / 95
|
Zero load power (W)
|
8 / 10
|
8 / 10
|
8 / 10
|
9 / 11
|
20 / 20 / 25
|
30 / 35
|
Zero load power in AES mode (W)
|
5 / 8
|
5 / 8
|
5 / 8
|
7 / 9
|
15 / 15 / 20
|
25 / 30
|
Zero load power in Search mode (W)
|
2 / 3
|
2 / 3
|
2 / 3
|
3 / 4
|
8 / 10 / 12
|
10 / 15
|
CHARGER
|
AC Input
|
Input voltage range: 187-265 VAC Input frequency: 45 - 65 Hz Power factor: 1
|
Charge voltage 'absorption' (V DC)
|
14,4 / 28,8 / 57,6
|
Charge voltage 'float' (V DC)
|
13,8 / 27,6 / 55,2
|
Storage mode (V DC)
|
13,2 / 26,4 / 52,8
|
Charge current house battery (A) (4)
|
35 / 16
|
50 / 25
|
70 / 40
|
80 / 50
|
120 / 70 / 35
|
120 / 70
|
Charge current starter battery (A)
|
4 (12 V and 24 V models only)
|
Battery temperature sensor
|
yes
|
GENERAL
|
Auxiliary output (5)
|
n. a.
|
n. a.
|
n. a.
|
n. a.
|
Yes (16A)
|
Yes (50A)
|
Programmable relay (6)
|
Yes
|
Protection (2)
|
a - g
|
VE.Bus communication port
|
For parallel and three phase operation, remote monitoring and system integration
|
General purpose com. port
|
n. a.
|
n. a.
|
n. a.
|
n. a.
|
Yes
|
Yes
|
Remote on-off
|
Yes
|
Common Characteristics
|
Operating temp. range: -40 to +65°C (fan assisted cooling) Humidity (non-condensing): max 95%
|
ENCLOSURE
|
Common Characteristics
|
Material & Colour: aluminium (blue RAL 5012) Protection category: IP 21
|
Battery-connection
|
battery cables of 1.5 meter
|
M8 bolts
|
Four M8 bolts (2 plus and 2 minus connections)
|
230 V AC-connection
|
G-ST18i connector
|
Spring-clamp
|
Screw terminals 13 mm2 (6 AWG)
|
M6 bolts
|
Weight (kg)
|
10
|
10
|
10
|
12
|
18
|
30
|
Dimensions (hxwxd in mm)
|
375 x 214 x 110
|
520 x 255 x 125
|
362 x 258 x 218
|
444 x 328 x 240
|
STANDARDS
|
Safety
|
EN-IEC 60335-1, EN-IEC 60335-2-29, IEC 62109-1
|
Emission, Immunity
|
EN 55014-1, EN 55014-2, EN-IEC 61000-3-2, EN-IEC 61000-3-3, IEC 61000-6-1, IEC 61000-6-2, IEC 61000-6-3
|
Road vehicles
|
12V and 24V models: ECE R10-4
|
1) Can be adjusted to 60 HZ. 120 V models available on request
2) Protection key:
a) output short circuit
b) overload
c) battery voltage too high
d) battery voltage too low
e) temperature too high
f) 230 VAC on inverter output
g) input voltage ripple too high
3) Non-linear load, crest factor 3:1
4) At 25?C ambient
5) Switches off when no external AC source available
6) Programmable relay that can a.o. be set for general alarm, DC under voltage or genset start/stop function AC rating: 230 V/4A DC rating: 4 A up to 35 VDC, 1 A up to 60 VDC
7) A.o. to communicate with a Lithium Ion battery BMS
|
|
|
|
|
|
|
|