The VE Transfer Switch automatically switches between different power sources: between a generator and shore power, between an inverter and a generator or between an inverter and shore power.
The VE Transfer Switch has two inputs and one output, it automatically transfers the available AC power to the output.
The VE Transfer Switch is available in two models:
5KVA, single phase, 200-250Vac
10KVA, single phase, 200-250Vac
Models:
5 kVA, 10 kVA
| VE TRANSFER SWITCH |
COS 0 - 5kVA |
COS 0 - 10kVA |
| Nominal voltage |
200 - 250V AC, Single phase |
| Nominal frequency |
50 – 60 Hz |
| Input 1, Nom. current |
20 A |
40 A |
| Input 2, Nom. current |
20 A |
40 A |
| Output, Nom. current |
20 A |
40 A |
| Max. motor (airco) power |
1,3 kW |
8 kW |
| Power consumption Input 1 |
6 VA |
6 VA |
| Power consumption Input 2 |
0 VA |
0 VA |
| Transfer time by closing contacts |
10 – 20 msec. |
10 – 20 msec. |
| Transfer time by opening contacts |
5 – 20 msec. |
5 – 20 msec. |
| Transfer time by closing contacts |
10 – 20 msec. |
10 – 20 msec. |
| Contacts delay Input 1 |
Approximately 10 sec. (adjustable) |
| Auxiliary contact |
200 - 240V AC; 20 A, cos ɸ =1 |
| GENERAL |
| Operating temperature |
-5°C to + 60°C |
| Humidity (non-condensing) |
Max. 95% |
| Miniature circuit breaker (MCB) |
Not included – installation dependent |
| Earth leakage breakers (RCD) |
Not included – installation dependent |
| ENCLOSURE |
| Protection category |
IP 54 |
| Colour |
RAL 7035 |
| Dimension h x w x d (mm) |
175 x 215 x 120 |
175 x 215 x120 |
|
|
 |
 |
 |
 |

|