The MultiPlus, as the name suggests, is a combined inverter and charger in one elegant package. Its many features include a true sine wave inverter, adaptive charging, hybrid PowerAssist technology, plus multiple system integration features.
Models:
2000VA
Unique PowerAssist feature
The MultiPlus will prevent overload of a limited AC source, such as a generator or shore power connection. First, battery charging will automatically be reduced when otherwise an overload would occur. The second level will boost the output of a generator or shore side supply with power taken from the battery.
Uninterrupted AC power (UPS function)
In the event of a grid failure, or when shore or generator power is disconnected, the inverter within the Multi is automatically activated and takes over the supply to the connected loads. This happens so fast (less than 20 milliseconds) that computers and other electronic equipment will continue to operate without disruption.
Virtually unlimited power thanks to parallel operation
Up to 6 units can operate in parallel to achieve higher power output. Three phase or split phase operation is also possible.
Remote Monitoring and Control
When coupled with a GX device (e.g. Cerbo GX) you can monitor and control your MultiPlus and system or systems locally (via LAN) or remotely (via the internet) from anywhere in the world, using the free VRM app and the free VRM portal website. Access can be from a phone, tablet, laptop or PC for multiple operating systems. There is no end to the level of control, from adjusting your MultiPlus to auto starting a backup generator and more...
|
MultiPlus 12/2000/80-50
|
MultiPlus 24/2000/50-50
|
MultiPlus 48/2000/25-50
|
PowerControl / PowerAssist
|
Yes
|
Three Phase and parallel operation
|
Yes
|
Transfer switch
|
50 A
|
INVERTER
|
Input voltage range
|
9,5 - 17 V
|
19 - 33 V
|
38- 66 V
|
Output
|
Output voltage: 120VAC ± 2% Frequency: 60Hz ± 0,1% (1)
|
Cont. output power at 25°C (3)
|
2000 VA
|
Cont. output power at 25°C
|
1600 W
|
Cont. output power at 40°C
|
1400 W
|
Cont. output power at 65°C
|
1000 W
|
Peak power
|
3500 W
|
Maximum efficiency
|
93%
|
94%
|
95%
|
Zero-load power
|
10 W
|
11 W
|
11 W
|
Zero-load power in search mode
|
3 W
|
4 W
|
4 W
|
CHARGER
|
AC Input
|
Input voltage range: 95-140 VAC Input frequency: 45 - 65 Hz
|
Charge voltage 'absorption'
|
14,4 / 28,8 / 57,6 V
|
Charge voltage 'float'
|
13,8 / 27,6 / 55,2 V
|
Storage mode
|
13,2 / 26,4 /52,8 V
|
Charge current house battery (4)
|
80 A
|
50 A
|
25 A
|
Charge current starter battery
|
1A (12 V and 24 V models only)
|
Battery temperature sensor
|
Yes
|
GENERAL
|
Programmable relay (5)
|
Yes
|
Protection (2)
|
a - g
|
VE.Bus communication port
|
For parallel and three phase operation, remote monitoring, and system integration
|
Remote on-off
|
On/off
|
DIP switches
|
Yes (7)
|
Internal DC fuse
|
no
|
Common Characteristics
|
Operating temp. range: -40 to +65°C (fan assisted cooling) Humidity (non-condensing): max 95%
|
ENCLOSURE
|
Common Characteristics
|
Steel (RAL 5012), IP22
|
Battery-connection
|
M8 bolts
|
230V AC-connection
|
Screw terminals 13 mm2 (6 AWG)
|
Weight
|
15.5 kg
|
Dimensions (h x w x d)
|
506 x 236 x 147 mm
|
STANDARDS
|
Safety
|
EN-IEC 60335-1, EN-IEC 60335-2-29, EN 62109-1
|
Emission Immunity
|
EN 55014-1, EN 55014-2, EN-IEC 61000-3-2, EN-IEC 61000-3-3, IEC 61000-6-1, IEC 61000-6-2, IEC 61000- 6-3
|
Automotive Directive
|
ECE R10-5
|
1) Can be adjusted to 50Hz
2) Protection:
a. Output short circuit
b. Overload
c. Battery voltage too high
d. Battery voltage too low
e. Temperature too high
f. 230VAC on inverter output
g. Input voltage ripple too high
3) Non-linear load, crest factor 3:1
4) At 25°C ambient
5) Programmable relay which can be set for: general alarm, DC under voltage or generator start/stop signal function AC rating: 230V/4A DC rating: 4A up to 35VDC, 1A up to 60VDC
6) Remote / battery charge voltage / inverter frequency /search mode
7) Battery charge voltage / search mode
|
|
|
|
|
|
|
|