Filax 2
|
230V/50Hz
|
240V/60Hz
|
110V/50Hz
|
120V/60Hz
|
|
Maximum current
|
16A
|
|
Priority source: low voltage switching threshold
|
180V
|
180V
|
88V
|
90V
|
|
Priority source: low voltage reverse switching threshold
|
188V
|
188V
|
92V
|
94V
|
|
Priority source: low frequency switching threshold
|
45Hz
|
46Hz
|
45Hz
|
46Hz
|
|
Priority source: low frequency reverse switching threshold
|
47Hz
|
52Hz
|
47Hz
|
52Hz
|
|
Priority source: high frequency switching threshold
|
60Hz
|
68Hz
|
62Hz
|
68Hz
|
|
Priority source: high frequency reverse switching threshold
|
56Hz
|
63Hz
|
58Hz
|
63Hz
|
|
Priority source: maximum continuous input voltage
|
260V
|
260V
|
130V
|
130V
|
|
Alternate source: maximum continuous input voltage
|
260V
|
260V
|
130V
|
130V
|
|
Maximum load transfer time and reverse transfer time
|
16ms
|
|
Reverse switching delay (seconds) 30s Operating temperature range
|
-20 to +50°C
|
|
Humidity (non-condensing)
|
Max 95%
|
|
LED indicators
|
|
Load supplied by priority source
|
Yellow
|
|
Load supplied by alternate source
|
Yellow
|
|
Priority source fault
|
Red
|
|
ENCLOSURE
|
|
Material & Colour
|
ABS RAL7035
|
|
Protection category
|
IP 65
|
|
Weight
|
0,8kg
|
Dimensions
(h x w x d)
|
120 x 255 x 75mm
|
|
STANDARDS
|
|
Safety
|
EN 60335-1, EN 60335-2-29
|
|
Emission, Immunity
|
EN 55014-1, EN 55014-2, EN 61000-3-3, EN 61000-6-3, EN 61000-6-2, EN 61000-6-1
|